A variable frequency drive, which is also called VFD, is used for controlling the frequency of the electrical power supplied to AC electric motor, thus controlling the rotational speed of the motor. Variable frequency drives are also known as adjustable frequency drives (AFD), variable-speed drives (VSD), AC drives, microdrives or inverter drives. These drives are sometimes also called variable voltage variable frequency (VVVF) drives, for the voltage is varied along with frequency. A variable frequency drive system generally consists of an AC motor, a controller and an operator interface.






Definition of HARSVERT Variable Frequency Drive model
Model is explained as follows:


Note:
1 Rated output current is □□□A, including 3 digital bits.
2 Rated output voltage: 03-3kV; 03.3-3.3kV; 04.16-4.16kV; 06-6kV; 06.6-6.6kV; 10-10kV;
11-11kV.
3 Control mode: A- asynchronous motor; S-synchronous motor; VA-asynchronous motor vector control; VS- synchronous motor vector control; FVA-asynchronous motor, regenerative drive; FVS-synchronous motor, regenerative drive;
For example:


HARSVERT Variable Frequency Drive parameters
| Item | Parameter |
| Standard | IEC61800-4:2002 Q/CP BLH003-2007 |
| Input | |
| Phase, frequency | Three phase, 50/60Hz |
| Allowable range of frequency fluctuation | ±10% |
| Allowable range of voltage fluctuation | ±10% |
| Input power factor | >0.95 (at more than 20% load) |
| Output | |
| Output voltage range | 3kV~11kV |
| Output current range | 25A~600A |
| VFD capacity | 280kW~8000kW |
| Over-load capacity | 120% of rated current for 60 seconds per 10minutes; 150% of rated current for 3s; 200% immediately |
| Output frequency | 0.5-120Hz |
| Basic performance | |
| Efficiency | ≥96% (including phase-shifting transformer) |
| Harmonics | Comply with IEEE 519 standard |
| Frequency resolution | 0.01Hz |
| Touch screen HMI | Output frequency, voltage, current, power; input voltage, current, power, power factor; failure/alarm; log; parameter setup; waveform display, etc. |
| Control | |
| Control mode | V/F control; Vector control |
| Acceleration/deceleration time | 0~3200s, Adjustable |
| Digital I/O | 5/5channels digital inputs/outputs; extendable |
| Communication port and protocols | RS485; Modbus-RTU[OPTIONAL Protocols: Profibus-DP, TCP/IP, DeviceNet, GPRS wireless transmission] |
| Control signal between Power cell and Controller | Connected by optical fibre |
| Auxiliary power supply | Single phase AC110V/ AC220V/ AC230V; or DC220V Capacity: 3kVA |
| PID function | Embedded PID regulator |
| Control function | Auto re-start after the recovery of main medium voltage; Torque booster; Frequency-skip; Self-diagnosis; Fly-start; Synchronous transfer[OPTIONAL]; Cell bypass[OPTIONAL] |
| Operation | |
| Operation mode | Local/Remote; Open loop/Close loop |
| Frequency given | Manually setting in the interface/Analog signal |
| Status output of VFD | analog output and digital output |
| Ambience | |
| Work field | Inside without corrosive and explosive gas and without dust, Altitude of below 1000m. |
| Temperature/humidity | Temperature: 0~+45oC; Humidity: below 90%, no condensation |
| Storage condition | -25~+55℃ |
| Others | |
| Protection | Over current, Short circuit, Earth fault, Over voltage, Low voltage, Over load, Over heat, Phase loss. |
| Enclose | IP20~IP41 |
| Cooling | Air cooling/Hot air to Chiller water heater exchanger cooling |
Application field
HARSVERT- series of medium voltage VFD can usually be applied in these fields:
Power generation: induced draft fans, forced draft fans, condensate exhausting pump, boiler feed water pumps, primary fan, secondary fan, circulating pump, mill fan, slurry pump, mill ...
System principle
System configuration
Multi-level voltage source VFD with the technology of cascade-connected power cells can directly output medium voltage, i.e. 3kV, 3.3kV, 4.16kV, 6kV, 6.6kV, 10kV and 11kV. VFD is composed of phase-shifting transformer, power cells and controller ...
Main Features
Normal start
At normal start status, VFD will start and operate at given frequency in open loop mode, or operate at the expected value of the controlled object in closed loop mode.
Soft start
At soft start status, VFD will start and accelerate to the frequency of power grid regardless of the given frequency. When the output frequency of VFD reaches the frequency of power grid (set in main interface) ...
Technical Data
1 Rated output current is □□□A, including 3 digital bits.
2 Rated output voltage: 03-3kV; 03.3-3.3kV; 04.16-4.16kV; 06-6kV; 06.6-6.6kV; 10-10kV; 11-11kV.
3 Control mode: A- asynchronous motor; S-synchronous motor; VA-asynchronous motor vector control ...